|
|
Correct Installation of Hard-Wired Surge Suppressors It is very important to follow the manufacturer’s installation instructions. Pay particular attention to fusing or breaker requirements and lead lengths. It is also important that the electrical distribution system be grounded and bonded per the National Electrical Code®. Failure to do so may result in damage to the surge suppressor. The performance of parallel-connected transient voltage surge suppressors is affected by the connecting leads. Both the wire size and length used to connect the suppressor will influence its performance. The voltage drop (V = L di/dt) across the connecting leads is added to the voltage across the suppression elements thus degrading the suppressors performance by increasing the residual voltage.
Figure 1. Suppression performance is a function of the connecting lead length. Self-inductance of wiring is proportional both to its length and to the logarithm of its thickness. Halving the length of connecting wires halves the inductance, but the thickness would have to be increased tenfold to achieve the same effect. Stranded wires have greater effective thickness than equivalent sized solid conductors because of skin effect on the total surface area. Thick, short, stranded connecting wires will give the best suppressor performance. However, short length is much more important than large wire size.
Figure 2. Example of Installation Procedure
Locate the surge suppressor as close as possible to the panel to be protected. NOTE: This example represents one of many acceptable ways to install hard-wired SPDs. Check with the manufacturer for suggested installation procedures.
NEXT: Regulatory, safety, &
standards >>
|
|
© 2002 National Electrical Manufacturers Association. Terms & Conditions of Use. Contact Webmaster. |